PRODUCT DETAIL
ELECTRICAL SPECIFICATIONS
Model | HB48100 |
Nominal Voltage | 51.2V |
Nominal Capacity | 100Ah |
Energy | 5120Wh |
Self Discharge | <3%/month |
Series or Parallel Connection | 16pcs in parallel |
MECHANICAL SPECIFICATIONS
Dimensions (L x W x H) | 440*435*222mm (17.3x17.1x8.74”) |
Weight | 54.5kg (120.1 lbs) |
Communication Interface | RS485 (Optional) |
Case Material | Metal |
Enclosure Protection | IP54 |
Cell Type - Chemistry | prismatic |
Chemistry | LiFePO4 |
CHARGE SPECIFICATIONS
Recommended Charge Current | 10A-60A |
Maximum Charge Current | 100A |
Charge Current (-20 to -10 ºC) | ≤0.05C |
Recommended Charge Voltage | 56V-57.6V |
BMS Charge Voltage Cut-Off | 57.6V (3.75±0.025vpc) |
Reconnect Voltage | 54.6V (3.34 ±0.05vpc) |
DISCHARGE SPECIFICATIONS
Maximum Continuous Discharge Current | 100A |
Peak Discharge Current | 105A (<5s) |
BMS Discharge Current Cut-Off | 105A |
Recommended Low Voltage Disconnect | 45V |
BMS Discharge Voltage Cut-Off | 43.2V (2.5±0.05vpc) |
Reconnect Voltage | 51.2V (2.9±0.1vpc) |
TEMPERATURE SPECIFICATIONS
Discharge Temperature | '-20 to 60ºC (-4 to 140 ºF) |
Charge Temperature | 0 to 45ºC (32 to 113 ºF) |
Storage Temperature (1month) | '-20 to 60ºC (-4 to 140 ºF) |
Storage Temperature (3months) | '-20 to 45ºC (-4 to 113 ºF) |
Storage Temperature (6months) | '-20 to 25ºC (-4 to 77 ºF) |
COMPLIANCE SPECIFICATIONS
Certifications | CE (pack), UN3480/MSDS (cell) |
Shipping Classification | UN3480, Class 9 |
Applicable to
Home energy storage, backup power supply |
DIMENSION SPECIFICATION
capacity indication:
state | charging | discharging | |||||||
---|---|---|---|---|---|---|---|---|---|
capacity indicator | L1● | L2● | L3● | L4● | L1● | L2● | L3● | L4● | |
0~25% | Lights off | Lights off | Lights off | light flashes2 | Lights off | Lights off | Lights off | Always bright | |
25~50% | Lights off | Lights off | light flashes 2 | Always bright | Lights off | Lights off | Always bright | Always bright | |
50~75% | Lights off | light flashes 2 | Always bright | Always bright | Lights off | Always bright | Always bright | Always bright | |
75~100% | light flashes2 | Always bright | Always bright | Always bright | Always bright | Always bright | Always bright | Always bright | |
Running lights● | Always bright | light flashes 3 |
Status indication:
system status | abnormal event | RUN | ALM | ALM Battery LED | |||
● | ● | ● | ● | ● | ● | ||
shutdown | Lights off | Lights off | All Lights off | ||||
Standby | normal | light flashes 1 | Lights off | According to the battery indicator | |||
alert | light flashes 1 | light flashes 2 | |||||
Charging | normal | Always bright | Lights off |
Indication by battery level
(up to LED light flashes 2) |
|||
alert | Always bright | light flashes 2 | |||||
Overcharge protection | Always bright | Lights off | all Always bright | ||||
temperature protection | light flashes 1 | light flashes 2 | According to the battery indicator | ||||
Failsafe | Lights off | Always bright | All Lights off | ||||
discharging | normal | light flashes 3 | Lights off | According to the battery indicator | |||
alert | light flashes 3 | light flashes 2 | |||||
Undervoltage protection | light flashes 3 | Lights off | All Lights off | ||||
Overcurrent and short circuit protection | Lights off | Always bright | All Lights off | ||||
invalid | Lights off | Always bright | All Lights off |
System management functions:
Cell and battery pack overvoltage, low voltage alarm and overvoltage, undervoltage protection. The voltage detection accuracy of the cell is ±10mV from 0°C to 45°C, ±20mV from -20°C to 0°C, and ±20mV from 45°C to 70°C.
Overcurrent alarm and protection of battery pack charge and discharge current, and battery pack output short circuit protection. The continuous charge and discharge current is 100A, the temperature rise is less than 50℃, and the current detection accuracy is better than 2%.
Real-time calculation of the remaining battery capacity, complete the learning of the total capacity of charging and discharging at one time, and the capacity estimation accuracy is better than 5%. Can automatically configure and record charging and discharging 2 Reignwood Xinde New Energy Co., Ltd. 3 cycles.
High temperature and low temperature alarms, high temperature and low temperature protection of battery cells, environment and power MOS. 6-channel temperature monitoring, including 4-channel cell temperature sensor, 1-channel ambient temperature sensor, 1-channel power MOS thermometer sensor, temperature detection accuracy is ±3℃.
Low internal resistance, high current, optimized design for large capacitive load startup, zero switching, and high charging withstand voltage for backup power applications.
The charge equalization strategy can be set flexibly, which can effectively improve the battery life and cycle life.
6 LEDs indicate remaining battery capacity, working mode and alarm protection status.
Intelligent one-key switch design, the system can be manually turned on when it is off, and can be manually turned off when it is not in the standby power state. Long press the button to reset the BMS by software or hardware and clear various abnormal states.
PC or intelligent front-end can realize battery data monitoring, operation control and parameter setting through commands such as telemetry, remote signaling, remote adjustment, and remote control. Realize the monitoring and management of battery cascade through RS485, and support RS232 communication and Modbus protocol at the same time.
The discharge MOS, charging MOS, current limiting function switch, buzzer alarm switch, forced sleep switch, etc. can be turned on and off through the host computer.
10A and 20A current limiting modules are optional, the host computer can set charging current limiting, or charging is not limited.
Various battery management parameters such as single battery overvoltage and undervoltage, total battery voltage overvoltage, charging overcurrent, discharging overcurrent, cell high and low temperature, environmental high and low temperature, equalization strategy, number of battery cells in series, and battery capacity can be passed through The upper computer is used to reset the settings.
The BMS design is equipped with a unique hardware watchdog protection circuit. Ensure that the BMS can operate safely and reliably for a long time in harsher environments.
The BMS system can be set to enable the system to perform real-time storage of operating data. For system monitoring, analysis and maintenance.
BMS system can realize online upgrade of system software through serial port.
It has the function of measuring the tilt angle of the gyroscope. When the product is moved and tilted at an angle (30°), the BMS controls the shutdown of the discharge MOS and prohibits the discharge, thereby realizing the anti-theft function.
When a short circuit occurs at the load end, the BMS has a short circuit protection function, which can quickly turn off the discharge MOS, cut off the loop, and activate the short circuit protection function. Recovery conditions for short-circuit protection: charging or manual recovery.
The BMS is equipped with a 4G/GPS function interface to expand the peripherals, and is equipped with a 4G/GPS module, which can remotely view the status of the BMS, realize real-time positioning of the BMS, and achieve the purpose of anti-theft.
The BMS has a display function interface and is equipped with a display module, which can view various data and status of the display.
With an anti-reverse connection circuit, when the positive and negative polarities of the external power supply are reversed to the positive and negative polarities of the BMS, the BMS will not be damaged and will alarm and enter the cut-off protection state. Recovery conditions for reverse connection protection: remove the power supply (back pressure) and release it immediately.
BMS has anti-surge function, which can suppress the surge impact of 4KV.
BMS is equipped with a dissolver function interface and is equipped with a dissolver module, which can trigger the fire signal according to the feedback signal of the dissolver, and achieve the function of early warning and fire prevention.
BMS Electrical Characteristics:
function name | function valid | item list | default value | setting description | setting |
---|---|---|---|---|---|
Cell voltage alarm | turn on | Overvoltage warning voltage | 3800 mV | Can be set | |
turn on | Overvoltage warning voltage | 2650 mV | Can be set | ||
Single Overvoltage Protection | turn on | Overvoltage Protection Voltage | 3750 mV | Can be set | |
Overvoltage protection delay | 1 S | Can be set | |||
Overvoltage protection recovery voltage | 3340 mV | Can be set | |||
Cell undervoltage protection | turn on | Undervoltage protection voltage | 2500 mV | Can be set | |
Undervoltage protection delay | 1 S | Can be set | |||
Brown-out recovery voltage | 2900 mV | Can be set | |||
Overall voltage alarm | turn on | Overvoltage warning voltage | 57V | Can be set | |
Undervoltage alarm voltage | 46V | Can be set | |||
Overall overvoltage protection | turn on | Overvoltage Protection Voltage | 57.6 V | Can be set | |
Overvoltage protection delay | 1 S | Can be set | |||
Overvoltage recovery voltage | 54.6 V | Can be set | |||
Overall undervoltage protection | turn on | Undervoltage protection voltage | 43.2 V | Can be set | |
Undervoltage protection delay | 1 S | Can be set | |||
Brown-out recovery voltage | 51.2 V | Can be set | |||
Cell temperature alarm | turn on | Charging high temperature alarm | 50℃ | Can be set | |
Charging low temperature alarm | 0 ℃ | Can be set | |||
Discharge high temperature alarm | 50 ℃ | Can be set | |||
Discharge low temperature alarm | 0 ℃ | Can be set | |||
Battery temperature forbidden to charge | turn on | Charging high temperature protection | 60 ℃ | Can be set | |
High temperature recovery after charging | 50 ℃ | Can be set | |||
Charging low temperature protection | -10 ℃ | Can be set | |||
low temperature recovery | 0 ℃ | Can be set | |||
Cell temperature forbidden | turn on | Discharge high temperature protection | 65 ℃ | Can be set | |
Discharge high temperature recovery | 50 ℃ | Can be set | |||
Discharge low temperature protection | -10 ℃ | Can be set | |||
Discharge low temperature recovery | 0 ℃ | Can be set | |||
Ambient temperature alarm | turn on | Ambient high temperature alarm | 50 ℃ | Can be set | |
Ambient low temperature alarm | 0 ℃ | Can be set | |||
MOS high temperature alarm | turn on | MOS high temperature alarm | 90 ℃ | Can be set | |
Charge overcurrent alarm | turn on | Charging alarm current | 95 A | Can be set | |
Charge overcurrent protection | turn on | Charge protection current | 105 A | Can be set | |
Charge overcurrent delay | 4 S | Can be set | |||
Discharge overcurrent alarm | turn on | Discharge alarm current | 95 A | Can be set | |
Discharge overcurrent protection | turn on | Discharge protection current | 105 A | Can be set | |
Discharge overcurrent delay | 5 S | Can be set | |||
Secondary discharge overcurrent protection | turn on | Secondary protection current | 130 A | Can be set | |
Secondary overcurrent delay | 500 mS | Can be set | |||
Output short circuit protection | turn on | Short circuit protection current | 330 A | ||
Short circuit protection delay | 500uS | ||||
Short circuit protection released | 1. The charging is released, and the charging current is ≥2A | ||||
Discharge overcurrent automatic recovery | Auto recovery delay | 15 mns | Automatic recovery after 15 minutes | ||
Cell balance function | turn on | Cell charge equalization | turn on Condition: Status of effective charge current | ||
Equalize turn on voltage | 3500 mV | Can be set | |||
Balance turn on differential pressure | 20 mV | Can be set | |||
Battery capacity setting | Battery rated capacity | 100Ah | Can be set | ||
turn on | Low battery warning | SOC alarm 1 is: 30 %(Can be set) | |||
Manual key setting | boot | BMS is in sleep state, press key for 1S to power on | |||
shutdown | BMS is not charging, press 3S to turn off | ||||
BMS power management | sleep time | 1440 Mins (no communication, no charge and discharge current) | Can be set |